DIN Rail Load Controller, 0-10V Dimmer, 16A, 100-277V for Zūm® Lighting Control with Net and Link Communication
Zūm® Wired DIN rail mounted load controllers with Zūm® Net communication designed to provide intelligent lighting control as part of a complete Zūm wired commercial room lighting system.
The Zūm® wired ZUMNET‑DIN‑16A‑LV provides 0-10V dimming for drivers and devices. The device can be wired to Zūm devices for network expansion and to Zūm Link devices for in-room control. Energy-saving options are available to enable daylighting, occupancy or vacancy sensing, and centralized monitoring and management. Room setup can be accomplished quickly through the Zūm app.
Zūm Net Wired Technology
In a Zūm network, Zūm Net load controllers facilitate communications between rooms via Ethernet and can be daisy‑chained for network expansion. Each device in the chain communicates to a Zūm Hub control system for centralized monitoring, management, and reporting. Zūm Link devices connect to Zūm Net devices to provide in‑room lighting control. Similar to the Zūm Wireless system, Zūm Link devices work together in a local ecosystem to provide customized solutions.
Zūm Link Wired Technology
Zūm Link technology enables in‑room lighting control through keypads and sensors wired to controllers. Zūm Wired devices connect via CBL-CAT5E-ZUMLINK-P CAT5e cable (sold separately) to RJ‑45 ports to provide simple daisy-chaining and lighting control of compatible loads. The Zūm Wired devices work together in a local ecosystem to provide customized solutions using the Zūm app.
Energy Management and Efficiency
The load controllers are capable of energy monitoring through custom programming. Occupancy sensor, vacancy sensor, and daylight sensor connectivity enables significant energy savings. To reduce energy usage, lights turn off automatically when the room is vacant and dim gradually depending on the amount of natural daylight in the room.
DIN Rail Mounting
DIN rail Zūm devices snap onto a standard DIN rail for installation in a wall mount enclosure (Crestron DIN‑EN series or similar) or on a wall panel.
Override Contact Closure Input
An integrated contact closure provides the means to place all connected Zūm Net and Zūm Link devices into Emergency Override mode.
Key Features
- Zūm® wired DIN rail mounted lighting load dimmer
- Dimming control of 0‑10V LED drivers or 4‑wire fluorescent ballasts
- Integration with Zūm keypads, presence detectors, and daylight sensors (sold separately)
- Ethernet network connection to ZUM‑HUB4 control system (sold separately)
- Integrated contact closure input
- 4M wide DIN rail mounting
Load Control |
Dim Load Types |
0-10V LED drivers or electronic ballasts (4‑wire) |
Dim Control Output |
0-10VDC, 60mA maximum sink or source |
Line Voltage |
100‑277VAC, 50/60 Hz |
Switch Load Types |
LED, electronic drivers, incandescent, magnetic low-voltage, electronic low-voltage,neon/cold cathode, high-intensity discharge, small motor loads |
Switch Rating |
16A 100-277VAC, 50/60 Hz;
1 HP @ 120-277VAC |
Switch Lifetime |
General Rating: 100,000 on/off operations, 16A @ 277VAC;
Motor Rating: 100,000 on/off operations, 1HP @ 120/230/277VAC |
Zūm Link Power Bus Requirements |
Max Current Consumption |
120mA With 0-10V load (60mA), without sensor terminal. |
Max Allowable Sensor Terminal Current |
85mA Passthrough from Zūm Link bus |
Wired Communications |
ZUMNET |
(2) RJ‑45 ports;
Input for control system connection or Zūm Net device;
Output for Zūm Net device daisy‑chaining |
ZUMLINK |
(2) RJ‑45 ports;
In‑room Zūm Link device daisy‑chaining |
24V, OCC, GND |
Occupancy sensor input;
Spring clamp connector;
Each terminal accepts one 20-24 AWG solid wire |
24V, PHO, GND |
Photo sensor input;
Spring clamp connector;
Each terminal accepts one 20-24 AWG solid wire |
OVR, GND |
Override control input;
Spring clamp connector:
Each terminal accepts one 20-24 AWG solid wire |
Controls and Indicators |
TEST |
(1) Pushbutton and (1) green LED;
Push to toggle the switched load output on and off;
Press and hold to cycle the dimming level up and down;
LED indicates that the load is turned on;
LED lights and flashes during room setup and factory reset |
ZUMLINK Status |
(1) bi‑color green/red LED;
LED lights green in normal operation;
LED lights red when a fault is detected |
ZUMNET Status |
(1) bi‑color green/red LED;
LED lights green in normal operation;
LED lights red when a fault is detected |
Connections |
N, L, SW
(Neutral, Line, Switch) |
(1) 3-pin terminal block;
Each terminal accepts one 12-24 AWG wire |
0‑10V |
(2) 0‑10VDC dimming control output;
Spring clamp connector;
Each terminal accepts one 12-24 AWG solid wire or 14-24 AWG stranded wire |
Environmental |
Local In-Cabinet Air Temperature |
32° to 131°F (0° to 55°C) |
Humidity |
10% to 90% RH (noncondensing) |
Heat Dissipation |
7 BTU/hr @ 0A;
13 BTU/hr @ 16A |
Construction |
Light gray polycarbonate housing with polycarbonate label overlay, 71 mm DIN rail mount, occupies 4M DIN module spaces, DIN 43380 for factor for enclosures with 45 mm front panel cutout |
Dimensions |
Height |
3.69 in. (94 mm) |
Width |
2.79 in. (71 mm) |
Depth |
2.32 in. (59 mm) |
Weight |
5 oz (142 g) |
Compliance |
Regulatory Model: M202231002 |
Intertek® Listed for US & Canada, CE, FCC Part 15 Class B, IC, WEEE |